General Specifications

Power Supply Voltage

  • 100 to 240 VAC (+10 %/-15 %)

Output Voltage of Power Supply

  • 24 VDC (±10 %; Output Capacity: 0.6 A)

Ambient Temperature

  • 0 to 55 °C (32 to 131 °F) (without freezing)

*1 *2

Storage Temperature

  • -25 to +75 °C (-13 to +167 °F)

Ambient Humidity

  • 5 to 95 % HR (without condensation)

*1

Withstand Voltage

  • 1500 VAC for 1 minute, between power terminals and I/O terminals, and between all external terminals and the housing

Noise Immunity

  • 1500 V peak-to-peak or more, pulse duration 1 µs, 50 ns (based on noise simulator), conforming to IEC standard (IEC61000-4-2/3/4/6)

Vibration Resistance

Intermittent Vibration

  • Frequency: 5 to 9 Hz
  • Amplitude: 3.5 mm (0.14")

*3 *4

Frequency: 9 to 150 Hz

  • Acceleration: 9.8 m/s2

*3 *4

Continuous Vibration

  • Frequency: 5 to 9 Hz
  • Amplitude: 1.75 mm (0.07")

*3 *4

Frequency: 9 to 150 Hz

  • Acceleration: 4.9 m/s2

*3 *4

Shock Resistance

  • Acceleration: 150 m/s2, application time: 11 ms; three times in each of the X, Y, and Z directions

Insulation Resistance

  • 50 MΩ or more (megohmmeter of 500 VCD used to perform measurements between power terminal and input terminals, and between all external terminals and the housing)

Operating Environment

As little dust and corrosive gas as possible

Operating Altitude

  • 2000 m (6600') or less

Overvoltage Category

  • AC: II, DC: I

Pollution Degree

  • 2

Performance Specifications

Calculation Control Method

Program Storage Method

I/O Control Method

Update Method

Programming Language

  • Expanded Ladder, KV Script, mnemonic

Number of Instructions

  • Basic Instruction: 81 types and 182 instructions, Application Instruction: 39 types and 56 instructions, Calculation Instruction: 123 types and 311 instructions, Expansion Instruction: 92 types and 141 instructions, Total: 335 types and 690 instructions

Instruction Execution Speed

  • Basic Instruction: 50 ns minimum, Application Instruction: 170 ns minimum

Program Capacity

  • 16k steps

Maximum Number of Connectable I/O Units

  • 8

Maximum Number of I/O Points

  • 256 (excluding I/O of the base unit)

Relay Specifications

Input/Output Relay/Internal Auxiliary Relay

  • Total: 9600 points 1 bit (R000 to R59915)

Retention Relay

  • B: 8192 points 1 bit (B0 to B1FFF)

Internal Auxiliary Relay

  • MR: 9600 points 1 bit (MR000 to MR59915)

Retention Relay

  • LR: 3200 points 1 bit (LR000 to LR19915)

Control Relay

  • CR: 1440 points 1 bit (CR000 to CR8915)

Timer

  • T: 512 points 32 bits (T0 to T511)

Counter

  • C: 256 points 32 bits (C0 to C255)

Data Memory

  • DM: 32768 points 16 bits (DM0 to DM32767)

Link Register

  • W: 16384 points 16 bits (W0 to W3FFF)

Temporary Memory

  • TM: 512 points 16 bits (TM0 to TM511)

High-Speed Counter

  • CTH: 4 points (CTH0 to CTH3)

32-Bit Automatic Reset Counter

*5

(Input response: 100 kHz per single phase, 50 kHz per phase difference)

*6

High-Speed Counter Comparator

  • CTC: 8 points (CTC0 to CTC7) 32 bits, two points per high-speed counter

Index Register

  • Z: 12 points 32 bits (Z01 to Z12)

Control Memory

  • CM: 9000 points 16 bits (CM0 to CM8999)

Base Unit I/O

  • Input: 36 points, Output: 24 points

Common Input: 1 point, Common Output: 8 points (type R), 3 point (type T/TP)

Number of Comments/Labels Stored in the Main Unit

  • Device Comment: 20000
  • Label: 28000

When writing a ladder program of maximum length, without labels.

Power-Off Retention Function

Program Memory

  • Can be rewritten 10000 times (Flash ROM)

Device

  • Non-volatile RAM

*7

Self-Diagnosis Function

  • CPU error, RAM error, and other problems

Input Specifications

Number of Relays

  • General Input: R000 to R007, R100 to R203 (28 points)

*8

  • High-Speed Phase A and Phase B Input: R008 to R015 (4 channels, 8 points in total)

Input Mode

  • 24 VCD (collector open)

Maximum Input Voltage

  • 26.4 VCD

Nominal Input Voltage

  • 24 VCD (General Input: 5.3 mA, High-Speed Phase A and Phase B Input: 6.5 mA)

*9

Minimum ON Voltage

  • 19 VCD

Maximum OFF Current

  • 1.5 mA

Common Point Mode

  • General Input: All points/1 common (1 terminal), High-Speed Phase A and Phase B Input: Shared common for all points (shared with general input)

Circuit Delay Time

  • General Input (for R108 to R203): OFF to ON: Max. 50 µs (Typ. 7 µs), ON to OFF: Max. 150 µs (Typ. 70 µs)
  • High-Speed Phase A and Phase B Input: OFF to ON: Max. 2 µs (Typ. 1.1 µs), ON to OFF: Max. 2 µs (Typ. 0.3 µs)

*10

Input Time Constant

  • Normal: 10 ms, When using the HSP instruction: 10 µs, When CR2305 is ON: 10 µs to 10 ms, eight-level switching possible (configured with CM1620). Can also be configured from the Unit Editor.

*10

Input Time Constant Delay

  • Input time constant adjustment 10 µs: Digital filter 1.6 to 2 µs, Input time constant adjustment 20 µs: Digital filter 9 to 12 µs, Input time constant adjustment 110 µs: Digital filter 90 to 93 µs, Input time constant adjustment 500 µs: Digital filter 300 to 400 µs, Input time constant adjustment 1 ms: Digital filter 800 to 900 µs, Input time constant adjustment 2.5 ms: Digital filter 2.3 to 2.4 ms, Input time constant adjustment 5 ms: Digital filter 4.0 to 4.5 ms, Input time constant adjustment 10 ms: Digital filter 9 to 9.5 ms

Response Frequency

(High-Speed Phase A and Phase B Input) Single phase: 100 kHz, phase difference: 50 kHz, 24 V ±10 %, Service 50 %

Output Specifications

Number of Relays

  • R500 to R607 (24 points)

Output Mode

  • Relay

Nominal Load

  • 250 V AC/30 V DC, 2 A

Common Point Mode

  • 2 to 4 points/1 common

ON/OFF Response Time

  • 10 ms or less

ON Resistance

  • 50 mΩ or less

Minimum Applicable Load

  • 100 µA/100 mVDC

Relay Life

  • Electrical: 100000 cycles or more (20 cycles/minute), Mechanical: 20000000 cycles or more

Relay Replacement

  • Impossible

Integrated Serial Port

Interface

  • Communication Standard: RS-232C

Connection

  • Modular Connector

RS-232C Transmission Specifications

  • Transmission Speed: 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 bps
  • Transmission Method: Full Duplex
  • Data Format: Start Bit 1 bit, Data Bits 7 bits, 8 bits, Stop Bit 1 bit, 2 bits, Parity Detection: None, Even, Odd

Transmission Distance

  • 15 m (49.2')

Number of Transmission Units

  • 1

Indication

  • SD (green), RD (red)

Internal Current Consumption

  • 91 VA (VA values are calculated with a power factor of 30 %.)

Weight

  • Approx. 820 g

*1 The guaranteed range as a system (excluding elements specifically indicated for the units and cassettes).

*2 The temperature below the center of the unit (30 mm (1.18") ), inside a control panel.

*3 These specifications correspond to situations in which the unit is mounted on a DIN rail, and in which the unit is mounted directly on the panel.

*4 Complies with JIS B 3502 and IEC61131-2, Scan times: 10 times (100 minutes) in each of the X, Y, and Z directions

*5 Also, settings can be configured so that automatic reset is not used.

*6 Only open collectors are supported. Line drivers are not compatible.

*7 The destination device can be configured by clicking “CPU system setting” and then “Power off holding” in KV STUDIO.

*8 The response time increases for R108 to R203.

*9 Reference value of the input current.

*10 The input response time, corresponding to the input time constant, can be calculated as follows: (Response Time) = (Input Circuit Delay) + (Delay by Digital Filter)

Example: Maximum response time, when the input time constant is set to 500 µs OFF to ON: 30 µs (circuit delay) + 400 µs (digital filter) = 430 µs ON to OFF: 50 µs (circuit delay) + 400 µs (digital filter) = 450 µs