Base Unit Type 60 Points AC Power Supply Relay
- Code / Model:
- Manufacturer: Keyence
- Department: Unclassified
- Category of products: Unclassified
- Sub-category: Unclassified
- You've seen it before.: 1
General Specifications
Power Supply Voltage
- 100 to 240 VAC (+10 %/-15 %)
Output Voltage of Power Supply
- 24 VDC (±10 %; Output Capacity: 0.6 A)
Ambient Temperature
- 0 to 55 °C (32 to 131 °F) (without freezing)
*1 *2
Storage Temperature
- -25 to +75 °C (-13 to +167 °F)
Ambient Humidity
- 5 to 95 % HR (without condensation)
*1
Withstand Voltage
- 1500 VAC for 1 minute, between power terminals and I/O terminals, and between all external terminals and the housing
Noise Immunity
- 1500 V peak-to-peak or more, pulse duration 1 µs, 50 ns (based on noise simulator), conforming to IEC standard (IEC61000-4-2/3/4/6)
Vibration Resistance
Intermittent Vibration
- Frequency: 5 to 9 Hz
- Amplitude: 3.5 mm (0.14")
*3 *4
Frequency: 9 to 150 Hz
- Acceleration: 9.8 m/s2
*3 *4
Continuous Vibration
- Frequency: 5 to 9 Hz
- Amplitude: 1.75 mm (0.07")
*3 *4
Frequency: 9 to 150 Hz
- Acceleration: 4.9 m/s2
*3 *4
Shock Resistance
- Acceleration: 150 m/s2, application time: 11 ms; three times in each of the X, Y, and Z directions
Insulation Resistance
- 50 MΩ or more (megohmmeter of 500 VCD used to perform measurements between power terminal and input terminals, and between all external terminals and the housing)
Operating Environment
As little dust and corrosive gas as possible
Operating Altitude
- 2000 m (6600') or less
Overvoltage Category
- AC: II, DC: I
Pollution Degree
- 2
Performance Specifications
Calculation Control Method
Program Storage Method
I/O Control Method
Update Method
Programming Language
- Expanded Ladder, KV Script, mnemonic
Number of Instructions
- Basic Instruction: 81 types and 182 instructions, Application Instruction: 39 types and 56 instructions, Calculation Instruction: 123 types and 311 instructions, Expansion Instruction: 92 types and 141 instructions, Total: 335 types and 690 instructions
Instruction Execution Speed
- Basic Instruction: 50 ns minimum, Application Instruction: 170 ns minimum
Program Capacity
- 16k steps
Maximum Number of Connectable I/O Units
- 8
Maximum Number of I/O Points
- 256 (excluding I/O of the base unit)
Relay Specifications
Input/Output Relay/Internal Auxiliary Relay
- Total: 9600 points 1 bit (R000 to R59915)
Retention Relay
- B: 8192 points 1 bit (B0 to B1FFF)
Internal Auxiliary Relay
- MR: 9600 points 1 bit (MR000 to MR59915)
Retention Relay
- LR: 3200 points 1 bit (LR000 to LR19915)
Control Relay
- CR: 1440 points 1 bit (CR000 to CR8915)
Timer
- T: 512 points 32 bits (T0 to T511)
Counter
- C: 256 points 32 bits (C0 to C255)
Data Memory
- DM: 32768 points 16 bits (DM0 to DM32767)
Link Register
- W: 16384 points 16 bits (W0 to W3FFF)
Temporary Memory
- TM: 512 points 16 bits (TM0 to TM511)
High-Speed Counter
- CTH: 4 points (CTH0 to CTH3)
32-Bit Automatic Reset Counter
*5
(Input response: 100 kHz per single phase, 50 kHz per phase difference)
*6
High-Speed Counter Comparator
- CTC: 8 points (CTC0 to CTC7) 32 bits, two points per high-speed counter
Index Register
- Z: 12 points 32 bits (Z01 to Z12)
Control Memory
- CM: 9000 points 16 bits (CM0 to CM8999)
Base Unit I/O
- Input: 36 points, Output: 24 points
Common Input: 1 point, Common Output: 8 points (type R), 3 point (type T/TP)
Number of Comments/Labels Stored in the Main Unit
- Device Comment: 20000
- Label: 28000
When writing a ladder program of maximum length, without labels.
Power-Off Retention Function
Program Memory
- Can be rewritten 10000 times (Flash ROM)
Device
- Non-volatile RAM
*7
Self-Diagnosis Function
- CPU error, RAM error, and other problems
Input Specifications
Number of Relays
- General Input: R000 to R007, R100 to R203 (28 points)
*8
- High-Speed Phase A and Phase B Input: R008 to R015 (4 channels, 8 points in total)
Input Mode
- 24 VCD (collector open)
Maximum Input Voltage
- 26.4 VCD
Nominal Input Voltage
- 24 VCD (General Input: 5.3 mA, High-Speed Phase A and Phase B Input: 6.5 mA)
*9
Minimum ON Voltage
- 19 VCD
Maximum OFF Current
- 1.5 mA
Common Point Mode
- General Input: All points/1 common (1 terminal), High-Speed Phase A and Phase B Input: Shared common for all points (shared with general input)
Circuit Delay Time
- General Input (for R108 to R203): OFF to ON: Max. 50 µs (Typ. 7 µs), ON to OFF: Max. 150 µs (Typ. 70 µs)
- High-Speed Phase A and Phase B Input: OFF to ON: Max. 2 µs (Typ. 1.1 µs), ON to OFF: Max. 2 µs (Typ. 0.3 µs)
*10
Input Time Constant
- Normal: 10 ms, When using the HSP instruction: 10 µs, When CR2305 is ON: 10 µs to 10 ms, eight-level switching possible (configured with CM1620). Can also be configured from the Unit Editor.
*10
Input Time Constant Delay
- Input time constant adjustment 10 µs: Digital filter 1.6 to 2 µs, Input time constant adjustment 20 µs: Digital filter 9 to 12 µs, Input time constant adjustment 110 µs: Digital filter 90 to 93 µs, Input time constant adjustment 500 µs: Digital filter 300 to 400 µs, Input time constant adjustment 1 ms: Digital filter 800 to 900 µs, Input time constant adjustment 2.5 ms: Digital filter 2.3 to 2.4 ms, Input time constant adjustment 5 ms: Digital filter 4.0 to 4.5 ms, Input time constant adjustment 10 ms: Digital filter 9 to 9.5 ms
Response Frequency
(High-Speed Phase A and Phase B Input) Single phase: 100 kHz, phase difference: 50 kHz, 24 V ±10 %, Service 50 %
Output Specifications
Number of Relays
- R500 to R607 (24 points)
Output Mode
- Relay
Nominal Load
- 250 V AC/30 V DC, 2 A
Common Point Mode
- 2 to 4 points/1 common
ON/OFF Response Time
- 10 ms or less
ON Resistance
- 50 mΩ or less
Minimum Applicable Load
- 100 µA/100 mVDC
Relay Life
- Electrical: 100000 cycles or more (20 cycles/minute), Mechanical: 20000000 cycles or more
Relay Replacement
- Impossible
Integrated Serial Port
Interface
- Communication Standard: RS-232C
Connection
- Modular Connector
RS-232C Transmission Specifications
- Transmission Speed: 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 bps
- Transmission Method: Full Duplex
- Data Format: Start Bit 1 bit, Data Bits 7 bits, 8 bits, Stop Bit 1 bit, 2 bits, Parity Detection: None, Even, Odd
Transmission Distance
- 15 m (49.2')
Number of Transmission Units
- 1
Indication
- SD (green), RD (red)
Internal Current Consumption
- 91 VA (VA values are calculated with a power factor of 30 %.)
Weight
- Approx. 820 g
*1 The guaranteed range as a system (excluding elements specifically indicated for the units and cassettes).
*2 The temperature below the center of the unit (30 mm (1.18") ), inside a control panel.
*3 These specifications correspond to situations in which the unit is mounted on a DIN rail, and in which the unit is mounted directly on the panel.
*4 Complies with JIS B 3502 and IEC61131-2, Scan times: 10 times (100 minutes) in each of the X, Y, and Z directions
*5 Also, settings can be configured so that automatic reset is not used.
*6 Only open collectors are supported. Line drivers are not compatible.
*7 The destination device can be configured by clicking “CPU system setting” and then “Power off holding” in KV STUDIO.
*8 The response time increases for R108 to R203.
*9 Reference value of the input current.
*10 The input response time, corresponding to the input time constant, can be calculated as follows: (Response Time) = (Input Circuit Delay) + (Delay by Digital Filter)
Example: Maximum response time, when the input time constant is set to 500 µs OFF to ON: 30 µs (circuit delay) + 400 µs (digital filter) = 430 µs ON to OFF: 50 µs (circuit delay) + 400 µs (digital filter) = 450 µs