KL5111 Harmonized Incremental-Encoder-Interface
Tweet
Follow @ADJDiTec
.
Si vous souhaitez une demande de devis pour ce produit, veuillez cliquer sur le bouton suivant.
Demander des prix
The KL5111 Bus Terminal is an interface for the direct connection of 24 V incremental encoders. A 16 bit counter with a quadrature decoder and a 16 bit latch for the zero pulse can be read, set or enabled. The state of the counter is transmitted quickly and securely to the PC, PLC or CNC over the fieldbus. Interval measurement with a resolution of 200 ns is possible. Up to 64 incremental encoders can be connected to a Bus Coupler.
Technical data | KL5111 | KS5111 |
---|---|
Technology | incremental encoder interface 24 V DC, EN 61131-2, type 1, “0”: < 5 V DC, ”1”: > 15 V DC, typ. 5 mA |
Number of channels | 1 incremental encoder |
Encoder connection | A, B, C, 24 V |
Encoder operating voltage | 24 V DC |
Encoder output current | – |
Counter | 16 bit, binary |
Limit frequency | 1 million increments/s (with 4-fold evaluation) |
Quadrature decoder | 4-fold evaluation |
Zero-pulse latch | 16 bit |
Commands | read, set, enable |
Power supply | 24 V DC (-15 %/+20 %) |
Supply voltage | 24 V DC (-15 %/+20 %) |
Current consumption power contacts | – |
Current consumption K-bus | typ. 40 mA |
Bit width in the process image | input/output: 2 x 16 bit data, 2 x 8 bit control/status |
Weight | approx. 60 g |
Operating/storage temperature | 0…+55 °C/-25…+85 °C |
Relative humidity | 95 %, no condensation |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. class/installation pos. | IP 20/variable |
Pluggable wiring | for all KSxxxx Bus Terminals |
Approvals | CE, UL, Ex |
Special terminals | |
---|---|
KL5111-0010 | A, B, C signals: 5 V inputs |
KL5111-0011 | special function: latch input sets counter to zero |
KL5111-0012 | latches on both edges, A, B, C inputs 24 V |
KL5111-0013 | latches on both edges, A, B, C inputs 5 V |
KL5111-0015 | frequency measurement over a selectable time window; 24 V inputs |
KL5111-0016 | frequency measurement over a selectable time window; 5 V inputs |
KL5111-0020 | 12 V input circuit |
Produits similaires
-
MONTRER
Détails.
11092748 Hy Zinc. Caja de 12 botes.
-
MONTRER
Détails.
Camozzi QP2A063A050W Ø63x50 SEALS IN VITON
-
MONTRER
Détails.
ABRAZADERA ASFA-L INOX W4 060-080 MM 03014107
-
MONTRER
Détails.
Herraje de Montaje para Cabezal A OP-76874 Keyence
-
MONTRER
Détails.
Festo 150418 IEN-M18B-PS-K-L Sensor de prox
-
MONTRER
Détails.
GEA 0021-3483-900 TRANSMISSION BAND