Temperature Input Unit Type 4-Point European Terminal Block
- Code / Model:
- Manufacturer: Keyence
- Department: Test and measurement
- Category of products: Measurement of temperature
- Sub-category: Digital thermometers
- You've seen it before.: 1
KV-NC4TP Data Sheet
This document provides specifications for the KV-NC4TP temperature input unit.
Model
KV-NC4TP
Number of Inputs
4
Input Type
- Thermocouple
- Platinum Resistance Thermometer
Input Range
Thermocouples
- K: -270.0 to 1372.0°C (-454 to 2501.6°F)
- J: -210.0 to 1200.0°C (-346 to 2192°F)
- T: -270.0 to 400.0°C (-454 to 752°F)
- E: -270.0 to 1000.0°C (-454 to 1832°F)
- N: -270.0 to 1300.0°C (-454 to 2372°F)
- R: -50.0 to 1768.0°C (-58 to 3214.4°F)
- S: -50.0 to 1768.0°C (-58 to 3214.4°F)
- B: 0.0 to 1820.0°C (32 to 3308°F)
- WRe5-26: 0.0 to 2315.0°C (32 to 4199°F)
Platinum Resistance Thermometers
- Pt100: -200.0 to 850.0°C (-328 to 1562°F)
- JPt100: -200.0 to 600.0°C (-328.0 to 1112.0°F)
General Accuracy
Thermocouples
±(0.2% of F.E. + 1°C (1.8°F)) (at 25°C ±5°C (77°F ±9°F))
±(0.4% of F.E. + 1°C (1.8°F)) (from 0 to 55°C (32 to 131°F))
Platinum Resistance Thermometers
±0.2% of F.E. (at 25°C ±5°C (77°F ±9°F))
±0.4% of F.E. (from 0 to 55°C (32 to 131°F))
Maximum Wiring Resistance
100 Ω max./wire (no variation allowed between three wires)
Conversion Speed
125 ms/channel
Isolation Method
- Between input terminals and base unit: Photocoupler/semiconductor relay/transformer isolation
- Between channels: (When a resistance thermometer is not used): Semiconductor relay isolation; (When a resistance thermometer is used): No isolation
Special Functions
- Channel omission, disconnection detection,
- Averaging (time average, count average, moving average),
- Special data compensation,
- Retention of peak/minimum value, alarm,
- Abnormal input configuration
Internal Current Consumption
40 mA or less
Weight
Approx. 110 g
*1 Can be configured individually for each channel.