Temperature Input Unit Type 4-Point European Terminal Block

Temperature Input Unit Type 4-Point European Terminal Block

KV-NC4TP Data Sheet

This document provides specifications for the KV-NC4TP temperature input unit.

Model

KV-NC4TP

Number of Inputs

4

Input Type

  • Thermocouple
  • Platinum Resistance Thermometer

Input Range

Thermocouples

  • K: -270.0 to 1372.0°C (-454 to 2501.6°F)
  • J: -210.0 to 1200.0°C (-346 to 2192°F)
  • T: -270.0 to 400.0°C (-454 to 752°F)
  • E: -270.0 to 1000.0°C (-454 to 1832°F)
  • N: -270.0 to 1300.0°C (-454 to 2372°F)
  • R: -50.0 to 1768.0°C (-58 to 3214.4°F)
  • S: -50.0 to 1768.0°C (-58 to 3214.4°F)
  • B: 0.0 to 1820.0°C (32 to 3308°F)
  • WRe5-26: 0.0 to 2315.0°C (32 to 4199°F)

Platinum Resistance Thermometers

  • Pt100: -200.0 to 850.0°C (-328 to 1562°F)
  • JPt100: -200.0 to 600.0°C (-328.0 to 1112.0°F)

General Accuracy

Thermocouples

±(0.2% of F.E. + 1°C (1.8°F)) (at 25°C ±5°C (77°F ±9°F))

±(0.4% of F.E. + 1°C (1.8°F)) (from 0 to 55°C (32 to 131°F))

Platinum Resistance Thermometers

±0.2% of F.E. (at 25°C ±5°C (77°F ±9°F))

±0.4% of F.E. (from 0 to 55°C (32 to 131°F))

Maximum Wiring Resistance

100 Ω max./wire (no variation allowed between three wires)

Conversion Speed

125 ms/channel

Isolation Method

  • Between input terminals and base unit: Photocoupler/semiconductor relay/transformer isolation
  • Between channels: (When a resistance thermometer is not used): Semiconductor relay isolation; (When a resistance thermometer is used): No isolation

Special Functions

  • Channel omission, disconnection detection,
  • Averaging (time average, count average, moving average),
  • Special data compensation,
  • Retention of peak/minimum value, alarm,
  • Abnormal input configuration

Internal Current Consumption

40 mA or less

Weight

Approx. 110 g

*1 Can be configured individually for each channel.