MU-N12 Model
Main Unit / Expansion Unit
This section provides specifications for the MU-N12 model.
Response Time
Depends on the connected sensor model. *1
Power Supply
- Voltage: 24 VDC, ripple (P-P) 10% or less, Class 2 or LPS
- Current Consumption: 55 mA or less (no load) *2
I/O
Control Output
4 max., NPN collector open/PNP collector open selectable, 24 V or less, Main Unit: 50 mA or less *3, Expansion Unit: 20 mA or less, Residual Voltage: 2 V or less, N.O./N.C. selectable *1 *4
External Input
5 max., Short-circuit Current: NPN: 1 mA or less, PNP: 2 mA or less, For applied voltage, see wiring diagrams (page 3 of the instruction manual) *1 *4
Analog Output
-
Protection Circuit
Protection against reverse power connection, power surges, output overcurrent, output spikes, and reverse output connection
Expansion Units
Up to 4 expansion units *5
Sensor Connection Specification
- Sensor Allowable Current: 150 mA or less
N-bus Connection Specification
- Pass Current Allowable: 900 mA or less
Environmental Resistance
- Ambient Temperature: -20 to +50 °C (-4 to 122 °F) (No freezing)
- Relative Humidity: 35 to 85% HR (No condensation)
Vibration Resistance
10 to 55 Hz, Double Amplitude 1.5 mm (0.06"), 2 hours in each of the X, Y, and Z directions
Shock Resistance
1,000 m/s2, 6 times in each of the X, Y, and Z directions
Material
- Case and Dust Cover: Polycarbonate
- Buttons: Polyacetal
- Display: PMMA
Weight
Approx. 70 g
Notes
- *1 The response time, as well as the types and number of inputs and outputs available, vary depending on the connected sensor model. For more information, refer to the "MU-N Series User Manual" specific to the model being connected.
- *2 1185 mA or less when a sensor is connected, 4 outputs (with load) are used, and expansion units are connected.
- *3 20 mA or less: When using the expansion unit.
- *4 For more information about the control output, external input, and analog output cable assignment, please refer to the "Power Supply Cable Pin Assignment" table on page 3 of this manual.
- *5 Up to 5 N-bus devices, including the main unit (or network unit), can be linked.