Technical Data
KL5001
Encoder connection
- Binary input: D+, D-
- Binary output: Cl+, Cl-
Power supply
- 24 V via power contacts
Current consumption power contacts
Typically 20 mA without encoder
Encoder supply
- 24 V DC (20 - 29 V DC) via power contacts
Current consumption from the K-bus
Typically 25 mA
Data transfer rate
Adjustable up to 1 MHz, 250 kHz preset
Serial input
- 24-bit width (adjustable)
Data direction
Read
Signal output
Differential signal (RS422)
Signal input
Differential signal (RS422)
Electrical isolation
500 V (K-Bus / signal voltage)
Bit width in process image
- Input: 1 x 32 bits of data (1 x 8 bits control/status optional)
Weight
approx. 60 g
Dimensions (W x H x D)
approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)
Mounting
on 35 mm mounting rail conforms to EN 60715
Permissible ambient temperature range during operation
-25°C ... + 60°C (extended temperature range)
Permissible ambient temperature range during storage
-40°C ... + 85°C
Permissible relative air humidity
95%, no condensation
Vibration / shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27, see also Installation instructions for enhanced mechanical load capacity
EMC immunity / emission
conforms to EN 61000-6-2 / EN 61000-6-4
Protection class
IP20
Installation position
variable
Approval
- CE, cULus,
- ATEX