KL5001 SSI Sensor Interface

KL5001 SSI Sensor Interface

Technical Data

KL5001

Encoder connection

  • Binary input: D+, D-
  • Binary output: Cl+, Cl-

Power supply

  • 24 V via power contacts

Current consumption power contacts

Typically 20 mA without encoder

Encoder supply

  • 24 V DC (20 - 29 V DC) via power contacts

Current consumption from the K-bus

Typically 25 mA

Data transfer rate

Adjustable up to 1 MHz, 250 kHz preset

Serial input

  • 24-bit width (adjustable)

Data direction

Read

Signal output

Differential signal (RS422)

Signal input

Differential signal (RS422)

Electrical isolation

500 V (K-Bus / signal voltage)

Bit width in process image

  • Input: 1 x 32 bits of data (1 x 8 bits control/status optional)

Weight

approx. 60 g

Dimensions (W x H x D)

approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)

Mounting

on 35 mm mounting rail conforms to EN 60715

Permissible ambient temperature range during operation

-25°C ... + 60°C (extended temperature range)

Permissible ambient temperature range during storage

-40°C ... + 85°C

Permissible relative air humidity

95%, no condensation

Vibration / shock resistance

conforms to EN 60068-2-6 / EN 60068-2-27, see also Installation instructions for enhanced mechanical load capacity

EMC immunity / emission

conforms to EN 61000-6-2 / EN 61000-6-4

Protection class

IP20

Installation position

variable

Approval

  • CE, cULus,
  • ATEX

Products Related