16-Point Entry Unit Screw Terminal Block

16-Point Entry Unit Screw Terminal Block

KV-N16EX Expansion Input Unit

This document provides specifications for the KV-N16EX expansion input unit.

External Connection Method

Terminal block

Input Terminals

24 VCD mode, 5 VCD mode

Maximum Input Voltage

26.4 VCD

Nominal Input Voltage

24 VCD mode: 5.3 mA

5 VCD mode: 1 mA

Minimum ON Voltage

24 VCD mode: 19 V

5 VCD mode: 3.5 V

Maximum OFF Current

24 VCD mode: 1.5 mA

Maximum OFF Voltage

5 VCD mode: 1.5 V

Common Point Mode

  • 16 points/1 common (2 terminals)

*1 The KV-N8EX and KV-N16EX have 2 COM terminals, but these are shared internally.

Input Time Constant (Four-Level Switching)

Input time constant adjustment

OFF to ON

  • Typ.: 25 µs: 10 µs
  • 300 µs: 240 µs
  • 1 ms: 1 ms
  • 10 ms: 10 ms

OFF to ON (Max.)

  • 25 µs: 50 µs
  • 300 µs: 290 µs
  • 1 ms: 1.2 ms
  • 10 ms: 11 ms

ON to OFF (Typ.)

  • 25 µs: 50 µs
  • 300 µs: 280 µs
  • 1 ms: 1 ms
  • 10 ms: 10 ms

ON to OFF (Max.)

  • 25 µs: 150 µs
  • 300 µs: 390 µs
  • 1 ms: 1.2 ms
  • 10 ms: 11 ms

Input Impedance

4.3 kΩ

Internal Current Consumption

20 mA or less

Weight

Approx. 220 g