THERMAL OVERLOAD 55-70A FITS LC1D80-D95

THERMAL OVERLOAD 55-70A FITS LC1D80-D95

Are you looking for a variant or equivalent?

We can help you locate related references or products outside the catalog.

Request help

Description of the LRD3361 THERMAL OVERLOAD Relay 55-70A FITS LC1D80-D95 Schneider

Introduction:

The thermal overload relay LRD3361 from Schneider Electric is a reliable and economical device designed to protect motors against temporary and prolonged overloads, ensuring optimal operation.

  • Type of Relay: LRD3361 Thermal Overload Relay
  • Fault Current Classification: Class 10A according to IEC 60947-4-1
  • Thermal Protection Adjustment Range: 55…70 A
  • Nominal Isolation Voltage [Ui]: Supply circuit, 600 V according to CSA and ULC; Supply circuit: 690 V according to IEC 60947-4-1
  • Fault Current Trip Threshold: 1.14 +/- 0.06 Ir according to IEC 60947-4-1
  • Auxiliary Contacts: 1NA + 1NC
  • Thermal Current Rating [Ith]: 5 A for signaling circuit, 0.72 A at 500 V AC-15, 0.06 A at 440 V DC-13 for signaling circuit
  • Nominal Operating Voltage [Ue]: 1000 VAC 0...400 Hz for supply circuit according to IEC 60947-4-1; 4 A gG and 4 A BS for signaling circuit
  • Nominal Surge Voltage [Uimp]: 6 kV
  • Phase Failure Sensitivity: Trip current 130% of Ir in phases, the last at 0
  • Pushbuttons: Red pushbutton - stop; Blue pushbutton - reset
  • Temperature Compensation: -20…60 °C
  • Supply Circuit: Screw terminals for 1 cable(s) 4…35 mm² flexible without terminal, with terminal and solid without terminal
  • Control Circuit: Screw terminals for 2 cables(s) 1…2.5 mm² flexible without terminal, with terminal and solid without terminal; 1.7 N.m in screw terminals of the supply circuit
  • Nominal Flame Resistance Voltage: V1 according to UL 94
  • Vibrations and Impacts:

Products Related