16-Point I/O Unit Screw Terminal Block Relay
- Code / Model:
- Manufacturer: Keyence
- Department: Reels and signal conditioning
- Category of products: Reels
- Sub-category: Electromechanical relay modules
- You've seen it before.: 1
KV-N8EXR Expansion Unit
This document provides specifications for the KV-N8EXR expansion unit.
Input Expansion Unit
Connection Method
Terminal block
Number of Inputs
8
Input Terminals
24 VCD mode, 5 VCD mode
Maximum Input Voltage
26.4 VCD
Nominal Input Voltage
24 VCD mode: 5.3 mA
5 VCD mode: 1 mA
Minimum ON Voltage
24 VCD mode: 19 V
5 VCD mode: 3.5 V
Maximum OFF Current
24 VCD mode: 1.5 mA
Maximum OFF Voltage
5 VCD mode: 1.5 V
Common Point Mode
8 points/1 common (1 terminal)
- *1 The input and output COM terminals are independent.
Input Time Constant (Four-Level Switching)
Input Time Constant Adjustment
- OFF to ON: Typ. 25 µs: 10 µs, 300 µs: 240 µs, 1 ms: 1 ms, 10 ms: 10 ms
- OFF to ON: Max. 25 µs: 50 µs, 300 µs: 290 µs, 1 ms: 1.2 ms, 10 ms: 11 ms
- ON to OFF: Typ. 25 µs: 50 µs, 300 µs: 280 µs, 1 ms: 1 ms, 10 ms: 10 ms
- ON to OFF: Max. 25 µs: 150 µs, 300 µs: 390 µs, 1 ms: 1.2 ms, 10 ms: 11 ms
Input Impedance
4.3 kΩ
Output Expansion Unit
Number of Outputs
8
Output Mode
Relay
Nominal Load
250 VCA/30 VCD 2A
Leakage Current in OFF State
―
Residual Voltage in ON State
―
Resistance in ON State
50 mΩ or less
Common Point Mode
4 points/1 common (2 terminals)
- *1 The KV-N8EXR has two output terminals for each of C1 and C2, respectively, but each pair is internally shared. (C1 and C2 are isolated)
Response Time
- OFF to ON: 10 ms or less
- ON to OFF: ―
Relay Life
- Electrical: 100,000 cycles or more (20 cycles/minute)
- Mechanical: 20,000,000 cycles or more
Relay Replacement
Impossible
Internal Current Consumption
60 mA or less
Weight
Approx. 230 g