Base Unit Type 14 Point Font CD Power Supply Relay
- Code / Model:
- Manufacturer: Keyence
- Department: Unclassified
- Category of products: Unclassified
- Sub-category: Unclassified
- You've seen it before.: 1
General Specifications
Power Supply Voltage
- 24 VCD (+10 %/-15 %)
Output Voltage of Power Supply
- ―
Ambient Temperature
- 0 to 55 °C (32 to 131 °F) (without freezing)
*1 *2
Storage Temperature
- -25 to +75 °C (-13 to +167 °F)
Ambient Humidity
- 5 to 95 % of HR (without condensation)
*1
Withstood Voltage
- 1500 V AC for 1 minute, between power terminals and I/O terminals, and between all external terminals and the casing
Noise Immunity
- 1500 V peak-to-peak or more, pulse duration 1 µs, 50 ns (based on noise simulator), conforming to IEC standard (IEC61000-4-2/3/4/6)
Vibration Resistance
Intermittent Vibration
- Frequency: 5 to 9 Hz
- Amplitude: 3.5 mm (0.14")
*3 *4
Frequency: 9 to 150 Hz
- Acceleration: 9.8 m/s2
*3 *4
Continuous Vibration
- Frequency: 5 to 9 Hz
- Amplitude: 1.75 mm (0.07")
*3 *4
Frequency: 9 to 150 Hz
- Acceleration: 4.9 m/s2
*3 *4
Shock Resistance
- Acceleration: 150 m/s2, application time: 11 ms; three times in each of the X, Y and Z directions
Insulation Resistance
- 50 MΩ or more (megohmmeter of 500 VCD used to perform measurements between power terminal and input terminals, and between all external terminals and the casing)
Operating Environment
As little dust and corrosive gas as possible
Operating Altitude
- 2000 m (6600') or less
Overvoltage Category
- AC: II, CD: I
Pollution Degree
- 2
Performance Specifications
Calculation Control Method
Program Storage Method
I/O Control Method
Update Method
Programming Language
- Expanded Ladder, KV Script, mnemonic
Number of Instructions
- Basic Instruction: 81 types and 182 instructions, Application Instruction: 39 types and 56 instructions
- Calculation Instruction: 123 types and 311 instructions, Expansion Instruction: 92 types and 141 instructions, Total: 335 types and 690 instructions
Instruction Execution Speed
- Basic Instruction: 50 ns minimum, Application Instruction: 170 ns minimum
Program Capacity
- 8k steps
Maximum Number of Connectable I/O Units
- 3
Maximum Number of I/O Points
- 128 (excluding the I/O of the base unit)
Relay Input/Output/Internal Auxiliary Relay
R
- Total of 9600 1-bit points (R000 to R59915)
Retention Relay
B
- 8192 1-bit points (B0 to B1FFF)
Internal Auxiliary Relay
MR
- 9600 1-bit points (MR000 to MR59915)
Retention Relay
LR
- 3200 1-bit points (LR000 to LR19915)
Control Relay
CR
- 1440 1-bit points (CR000 to CR8915)
Timer
T
- 512 32-bit points (T0 to T511)
Counter
C
- 256 32-bit points (C0 to C255)
Data Memory
DM
- 32768 16-bit points (DM0 to DM32767)
Link Register
W
- 16384 16-bit points (W0 to W3FFF)
Temporary Memory
TM
- 512 16-bit points (TM0 to TM511)
High-Speed Counter
CTH
- 2 points (CTH0 to CTH1)
32-bit Automatic Reset Counter*5
- (Input response: 100 kHz per single phase, 50 kHz per phase difference)
*6
High-Speed Counter Comparator
CTC
- 4 points (CTC0 to CTC3), 32 bits, two points per high-speed counter
Index Register
Z
- 12 32-bit points (Z01 to Z12)
Control Memory
CM
- 9000 16-bit points (CM0 to CM8999)
Base Unit of I/O
- Input: 8 points, Output: 6 points
Common Input: 1 point, Common Output: 4 points (type R), 1 point (type T/TP)
Number of Comments/Labels Stored in the Main Unit
Device Comment
- 10000
When writing a ladder program of maximum length, without labels.
Label
- 14000
When writing a ladder program of maximum length, without device comments.
Power-Off Retention Function
Program Memory
- Can be rewritten 10000 times (Flash ROM)
Device
- Non-volatile RAM
*7
Self-Diagnosis Function
- CPU error, RAM error, and other problems
Input Specifications
Number of Relays
- General Input: R000 to R003 (4 points), High-Speed Phase A and B Input: R004 to R007 (2 channels, 4 points in total)
Input Mode
- 24 VCD collector open
Maximum Input Voltage
- 26.4 VCD
Nominal Input Voltage
- 24 VCD (General Input: 5.3 mA, High-Speed Phase A and B Input: 6.5 mA)
*8
Minimum ON Voltage
- 19 VCD
Maximum OFF Current
- 1.5 mA
Common Point Mode
- General Input: All points/1 common (1 terminal), High-Speed Phase A and B Input: Common shared for all points (shared with general input)
Circuit Delay Time
General Input:
- OFF to ON: Max. 30 µs (Typ. 3.5 µs), ON to OFF: Max. 50 µs (Typ. 15 µs)
High-Speed Phase A and B Input:
- OFF to ON: Max. 2 µs (Typ. 1.1 µs), ON to OFF: Max. 2 µs (Typ. 0.3 µs)
*9
Input Time Constant
- Normal: 10 ms, When using the HSP instruction: 10 µs
- When CR2305 is ON: 10 µs to 10 ms, eight-level switching possible (configured with CM1620). Can also be configured from the Unit Editor.
*9
Input Time Constant Delay
- Input time constant adjustment 10 µs: Digital filter 1.6 to 2 µs
- Input time constant adjustment 20 µs: Digital filter 9 to 12 µs
- Input time constant adjustment 110 µs: Digital filter 90 to 93 µs
- Input time constant adjustment 500 µs: Digital filter 300 to 400 µs
- Input time constant adjustment 1 ms: Digital filter 800 to 900 µs
- Input time constant adjustment 2.5 ms: Digital filter 2.3 to 2.4 ms
- Input time constant adjustment 5 ms: Digital filter 4.0 to 4.5 ms
- Input time constant adjustment 10 ms: Digital filter 9 to 9.5 ms
Response Frequency
(High-Speed Phase A and B Input) Single phase: 100 kHz, phase difference: 50 kHz, 24 V ±10 %, Service 50 %
Output Specifications
Number of Relays
- R500 to R505 (6 points)
Output Mode
- Relay
Rated Load
- 250 V AC/30 V DC, 2 A
Common Point Mode
- 2 to 4 points/1 common
ON/OFF Response Time
- 10 ms or less
ON Resistance
- 50 mΩ or less
Minimum Applicable Load
- 100 µA/100 mVDC
Relay Life
- Electrical: 100000 cycles or more (20 cycles/minute), Mechanical: 20000000 cycles or more
Relay Replacement
- Impossible
Integrated Serial Port
Interface
- Communication Standard: RS-232C
Connection
- Modular connector
RS-232C Transmission Specifications
- Transmission Speed: 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 bps
- Transmission Method: Full duplex
- Data Format: Start bit 1 bit, Data bits 7 bits, 8 bits, Stop bit 1 bit, 2 bits, Parity: None, Even, Odd
Transmission Distance
- 15 m (49.2')
Number of Transmission Units
- 1
Indication
- SD (green), RD (red)
Internal Current Consumption
- 160 mA
Weight
- Approx. 350 g
*1 The guaranteed range as a system (excluding elements specifically indicated for the units and cassettes).
*2 The temperature below the center of the unit (30 mm (1.18")), inside a control panel.
*3 These specifications correspond to situations where the unit is mounted on a DIN rail, and in which the unit is mounted directly on the panel.
*4 Complies with JIS B 3502 and IEC61131-2, Scan times: 10 times (100 minutes) in each of the X, Y and Z directions
*5 Automatic reset can also be configured to not be used.
*6 Only open collector drivers are supported. Line controllers are not compatible.
*7 The destination device can be configured by clicking “CPU system setting” and then “Power off holding” in KV STUDIO.
*8 Reference value of the input current.
*9 The input response time, corresponding to the input time constant, can be calculated as follows: (Response Time) = (Input circuit delay) + (Delay by digital filter)
Example: Maximum response time, when the input time constant is set to 500 µs
- OFF to ON: 30 µs (circuit delay) + 400 µs (digital filter) = 430 µs
- ON to OFF: 50 µs (circuit delay) + 400 µs (digital filter) = 450 µs