General Specifications

Supply voltage

  • 100 to 240 VAC (+10 %/-15 %)

Output voltage of power supply

  • 24 VDC (±10 %; output capacity: 0.6 A)

Ambient temperature

  • 0 to 55 °C (32 to 131 °F) (without freezing)

*1 *2

Storage temperature

  • -25 to +75 °C (-13 to +167 °F)

Ambient humidity

  • 5 to 95 % HR (without condensation)

*1

Withstood voltage

  • 1500 VAC for 1 minute, between power terminals and I/O terminals, and between all external terminals and the casing

Noise immunity

  • 1500 V peak-to-peak or more, pulse duration 1 µs, 50 ns (based on noise simulator), conforming to IEC standard (IEC61000-4-2/3/4/6)

Vibration Resistance

Intermittent vibration

  • Frequency: 5 to 9 Hz
  • Amplitude: 3.5 mm (0.14")

*3 *4

Frequency: 9 to 150 Hz

  • Acceleration: 9.8 m/s2

*3 *4

Continuous vibration

  • Frequency: 5 to 9 Hz
  • Amplitude: 1.75 mm (0.07")

*3 *4

Frequency: 9 to 150 Hz

  • Acceleration: 4.9 m/s2

*3 *4

Shock Resistance

Acceleration: 150 m/s2, application time: 11 ms; three times in each of the X, Y and Z directions

Insulation Resistance

50 MΩ or more (megohmmeter of 500 VCD used to perform measurements between power terminal and input terminals, and between all external terminals and the casing)

Operating Environment

As little dust and corrosive gas as possible

Operating altitude: 2000 m (6600') or less

Overvoltage category: AC: II, DC: I

Pollution degree: 2

Performance Specifications

Calculation Control Method

Program Storage Method

I/O Control Method

Update Method

Programming Language

  • Expanded Ladder, KV Script, mnemonic

Number of Instructions

Basic instruction: 81 types and 182 instructions, Application instruction: 39 types and 56 instructions, Calculation instruction: 123 types and 311 instructions, Expansion instruction: 92 types and 141 instructions, Total: 335 types and 690 instructions

Instruction Execution Speed

  • Basic instruction: 50 ns minimum, Application instruction: 170 ns minimum

Program Capacity

8k steps

Maximum Number of Connectable I/O Units

3

Maximum Number of I/O Points

128 (excluding the I/O of the base unit)

Relay

  • Input/Output Relay/Internal Auxiliary Relay: R
  • Total of 9600 1-bit points (R000 to R59915)
  • Retentive Relay: B
  • 8192 1-bit points (B0 to B1FFF)
  • Internal Auxiliary Relay: MR
  • 9600 1-bit points (MR000 to MR59915)
  • Retentive Relay: LR
  • 3200 1-bit points (LR000 to LR19915)
  • Control Relay: CR
  • 1440 1-bit points (CR000 to CR8915)
  • Timer: T
  • 512 32-bit points (T0 to T511)
  • Counter: C
  • 256 32-bit points (C0 to C255)
  • Data Memory: DM
  • 32768 16-bit points (DM0 to DM32767)
  • Link Register: W
  • 16384 16-bit points (W0 to W3FFF)
  • Temporary Memory: TM
  • 512 16-bit points (TM0 to TM511)
  • High-Speed Counter: CTH
  • 2 points (CTH0 to CTH1)
  • 32-bit Auto-Reset Counter *5
  • (Input response: 100 kHz per single phase, 50 kHz per phase difference) *6
  • High-Speed Counter Comparator: CTC
  • 4 points (CTC0 to CTC3)
  • 32 bits, two points per high-speed counter
  • Index Register: Z
  • 12 32-bit points (Z01 to Z12)
  • Control Memory: CM
  • 9000 16-bit points (CM0 to CM8999)

Base Unit of I/O

Input: 8 points, Output: 6 points

Common Input: 1 point, Common Output: 4 points (type R), 1 point (type T/TP)

Number of Comments/Labels Stored in the Main Unit

  • Device Comment: 10000
  • When writing a ladder program of maximum length, without labels.
  • Label: 14000
  • When writing a ladder program of maximum length, without device comments.

Power-Off Retention Function

Program Memory: Can be rewritten 10000 times the Flash ROM

Device: Non-volatile RAM *7

Self-Diagnosis Function

CPU error, RAM error, and other problems

Input Specifications

Number of Relays

  • General Input: R000 to R003 (4 points), High-Speed Phase A and Phase B Input: R004 to R007 (2 channels, 4 points in total)

Input Mode

24 VCD input (open collector)

Maximum Input Voltage

26.4 VCD

Nominal Input Voltage

24 VCD (General Input: 5.3 mA, High-Speed Phase A and Phase B Input: 6.5 mA *8)

Minimum ON Voltage

19 VCD

Maximum OFF Current

1.5 mA

Common Point Mode

  • General Input: All points/1 common (1 terminal), High-Speed Phase A and Phase B Input: Common shared for all points (shared with general input)

Circuit Delay Time

  • General Input:
    • OFF to ON: Max. 30 µs (Typ. 3.5 µs), ON to OFF: Max. 50 µs (Typ. 15 µs)
  • High-Speed Phase A and Phase B Input:
    • OFF to ON: Max. 2 µs (Typ. 1.1 µs), ON to OFF: Max. 2 µs (Typ. 0.3 µs)

Input Time Constant

Normal: 10 ms, When using the HSP instruction: 10 µs, When CR2305 is ON: 10 µs to 10 ms, eight-level switching possible (configured with CM1620). Can also be configured from the Unit Editor. *9

Input Time Constant Delay

Time constant adjustment of 10 µs: Digital filter 1.6 to 2 µs, Time constant adjustment of 20 µs: Digital filter 9 to 12 µs, Time constant adjustment of 110 µs: Digital filter 90 to 93 µs, Time constant adjustment of 500 µs: Digital filter 300 to 400 µs, Time constant adjustment of 1 ms: Digital filter 800 to 900 µs, Time constant adjustment of 2.5 ms: Digital filter 2.3 to 2.4 ms, Time constant adjustment of 5 ms: Digital filter 4.0 to 4.5 ms, Time constant adjustment of 10 ms: Digital filter 9 to 9.5 ms

Response Frequency

(High-Speed Phase A and Phase B Input) Single phase: 100 kHz, Phase difference: 50 kHz, 24 V ±10 %, Service 50 %

Output Specifications

Number of Relays

  • R500 to R505 (6 points)

Output Mode

Relay

Rated Load

250 VAC/30 VCD, 2 A

Common Point Mode

2 to 4 points/1 common

ON/OFF Response Time

10 ms or less

Resistance in ON State

50 mΩ or less

Minimum Applicable Load

100 µA/100 mVCD

Relay Life

  • Electrical: 100000 cycles or more (20 cycles/minute), Mechanical: 20000000 cycles or more

Relay Replacement

Impossible

Integrated Serial Port

Interface

Communication Standard: RS-232C

Connection

Modular connector

RS-232C Transmission Specifications

  • Transmission Speed: 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 bps
  • Transmission Method: Full duplex
  • Data Format: Start bit 1 bit, Data bits 7 bits, 8 bits, Stop bit 1 bit, 2 bits, Error Detection: Parity, Odd, None

Transmission Distance

15 m (49.2')

Number of Transmission Units

1

Indication

SD (green), RD (red)

Internal Current Consumption

76 VA (VA values are calculated with a power factor of 30 %.)

Weight

Approx. 430 g

*1 The guaranteed range as a system (excluding elements specifically indicated for the units and cassettes). *2 The temperature below the center of the unit (30 mm (1.18") ), inside a control panel. *3 These specifications correspond to situations in which the unit is mounted on a DIN rail, and in which the unit is mounted directly on the panel. *4 Complies with JIS B 3502 and IEC61131-2, Scan times: 10 times (100 minutes) in each of the X, Y and Z directions *5 Settings can also be configured so that automatic reset is not used. *6 Only open collectors are supported. Line drivers are not compatible. *7 The destination device can be configured by clicking on “CPU system setting” and then on “Power off holding” in KV STUDIO. *8 Reference value of the input current. *9 The input response time, corresponding to the input time constant, can be calculated as shown below. (Response Time) = (Input circuit delay) + (Delay by digital filter) Example: Maximum response time, when the input time constant is set to 500 µs OFF to ON: 30 µs (circuit delay) + 400 µs (digital filter) = 430 µs ON to OFF: 50 µs (circuit delay) + 400 µs (digital filter) = 450 µs