BECKHOFF BC8100 | Bus Terminal Controller with integrated IEC 61131-3 PLC, 32 kbytes program memory, RS232C interface
Jeśli życzy sobie oferty na ten produkt, może ją otrzymać klikając poniższy przycisk.
Zapytać o cenę.BC8000, BC8050, BC8100, BC8150 | 485/ 232 Bus Terminal Controllers
The Bus Terminal Controllers BC8000 and BC8100 are Bus Couplers with integrated PLC functionality and have a free serial interface. In the case of the BC8000 controller it is an 485 interface, through which a number of serial devices can be addressed. The BC8100 controller has a 232 interface, with which peer-to-peer connection is possible. The programmable interface is suitable for the connection of serial devices. The protocol can be freely programmed, so that displays, scanners, measuring systems, BK8x00 or a PC can be connected. The serial interface then functions as a master. A serial terminal, which is removed after the programming, is needed in order to test the interface.
The “Compact” Bus Terminal Controllers BC8050 with serial 485 interface and BC8150 with serial 232 interface extend the Beckhoff small controller series by cost-optimised versions in a compact housing. An open serial protocol – like in the BK8x00 Bus Couplers – and the Modbus RTU/ASCII protocol are implemented. The address and the protocol are selected via the two rotary selection switches.
Controller for stand-alone applications
The Bus Terminal Controller is programmed using the TwinCAT programming system conforms to IEC 61131-3. The PLC programs can be written in five different programming languages (IL, FBD, LD, SFC, ST). In addition, TwinCAT offers extensive debug functionalities (breakpoint, single step, monitoring, …), which facilitate commissioning. It is also possible to perform adjustment and measurement of the cycle time. The inputs and outputs of the connected Bus Terminals are assigned in the PLC.
Data is exchanged with the interface on the Bus Terminal Controller with the aid of a control and status byte, through which a handshake must be executed. A serial communication function block for TwinCAT is available for this purpose.
PLC data | 485 | BC8000 | 485 | BC8050 | 232 | BC8100 | 232 | BC8150 |
---|---|---|---|---|
Programming | TwinCAT (via programming interface or fieldbus) | |||
Program memory | 32/96 kbytes | 48 kbytes | 32/96 kbytes | 48 kbytes |
Data memory | 32/64 kbytes | 32 kbytes | 32/64 kbytes | 32 kbytes |
Remanent data | 512 bytes | 2 kbytes | 512 bytes | 2 kbytes |
Runtime system | 1 PLC task | |||
PLC cycle time | approx. 3 ms for 1,000 instructions (without I/O cycle, K-bus) | |||
Programming languages | IEC 61131-3 (IL, LD, FBD, SFC, ST) | |||
Online change | – | yes | – | yes |
Technical data | BC8000 | BC8050 | BC8100 | BC8150 |
---|---|---|---|---|
Number of Bus Terminals | 64 | 64 (255 with K-bus extension) | 64 | 64 (255 with K-bus extension) |
Max. number of bytes fieldbus | 512 byte input and 512 byte output | |||
Max. number of bytes process image | 512 byte input and 512 byte output | |||
Digital peripheral signals | 512 inputs/outputs | 1,020 inputs/outputs | 512 inputs/outputs | 1,020 inputs/outputs |
Analog peripheral signals | 128 inputs/outputs | |||
Protocol | KS8000 protocol (open, serial protocol), customised serial protocols can be implemented. | KS8000 protocol (open, serial protocol) – Modbus RTU/Modbus ASCII can be selected via address switch. | KS8000 protocol (open, serial protocol), customised serial protocols can be implemented. | KS8000 protocol (open, serial protocol) – Modbus RTU/Modbus ASCII can be selected via address switch, serial ADS. |
Data transfer rates | 1.2 kbaud…57.6 kbaud | 1.2 kbaud…38.4 kbaud | 1.2 kbaud…57.6 kbaud | 1.2 kbaud…38.4 kbaud |
Bus interface | 485 D-sub | 485 D-sub | 232 D-sub | 232 D-sub |
Power supply | 24 V DC (-15 %/+20 %) | |||
Input current | 70 mA + (total K-bus current)/4, 500 mA max. | 320 mA max. | 70 mA + (total K-bus current)/4, 500 mA max. | 320 mA max. |
Starting current | 2.5 x continuous current | |||
Current supply K-bus | 1,750 mA | 1,000 mA | 1,750 mA | 1,000 mA |
Power contacts | 24 V DC max./10 A max. | |||
Electrical isolation | 500 V (power contact/supply voltage) | |||
Weight | approx. 170 g | approx. 100 g | approx. 170 g | approx. 100 g |
Operating/storage temperature | 0…+55 °C/-25…+85 °C | -25…+60 °C/-40…+85 °C | 0…+55 °C/-25…+85 °C | -25…+60 °C/-40…+85 °C |
Relative humidity | 95 %, no condensation | |||
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 | |||
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 | |||
Protect. class/installation pos. | IP 20/variable | |||
Approvals | CE, UL, Ex, GL | CE, UL, Ex | CE, UL, Ex, GL | CE, UL, Ex |
Accessories | |
---|---|
KS2000 | configuration software for extended parameterisation |
TX1200 | programming system conforms to IEC 61131-3 |
TS6340 | IEC 61131-3 software library for TwinCAT PLC for communication via serial devices |
KL6001-0020 | 232 Bus Terminal for testing the serial interface with 5 bytes of user data |
KL6021-0020 | 485 Bus Terminal for testing the serial interface with 5 bytes of user data |
Cordsets | cordsets and connectors |
Ordering information | Description |
---|---|
BC8000 | 485 Bus Terminal Controller for up to 64 Bus Terminals |
BC8050 | 485 “Compact“ Bus Terminal Controller for up to 64 Bus Terminals (255 with K-bus extension) |
BC8100 | 232 Bus Terminal Controller for up to 64 Bus Terminals |
BC8150 | 232 “Compact“ Bus Terminal Controller for up to 64 Bus Terminals (255 with K-bus extension) |
BX8000 | 232/ 485 Bus Terminal Controller for up to 64 Bus Terminals (255 with K-bus extension) |
BK8x00 | 232/ 485 Bus Coupler |
Related products | |
---|---|
IL230x-C810 | 232 PLC Box with IP-Link extension interface, IP 67 |
System | |
---|---|
485 | For further 485 products please see the system overview |
Produkty podobne
-
Pokazać.
Szczegóły
OMRON NT631CST153EV3 | NT631, TFT Color 10.4" (Beige)
-
Pokazać.
Szczegóły
LR-W. Sensor general de Contraste.
-
Pokazać.
Szczegóły
OMRON R88MG40030TS2 | Servomotor Serie G/SS2 motor 400W, 200V, 3000RPM, 1.3Nm, ENC ABS
-
Pokazać.
Szczegóły
OMRON EESV3CS | Herradura 3.4mm Vert 1mm Soldar
-
Pokazać.
Szczegóły
RJI DIN-rail outlet for keystone jacks Harting 09458510000
-
Pokazać.
Szczegóły
BRACKET F WIRE CONDUIT BRACKET F WIRE CONDUIT